Loop Calibrator Setpoints
Drive current plus 0/25/50/75/100% table.
Result
Drive current (mA)
12.000
Expected EU
50.000
Calculation details
Voltage on 250 ohm (V)
3.000
0% (mA)
4.00
25% (mA)
8.00
50% (mA)
12.00
75% (mA)
16.00
100% (mA)
20.00
EU per 25% step
25.000
Formula
Calculation logicVerify
Check before relying.
Drive the loop, watch the DCS.
- Calibrator in source mode powers the loop
- Simulate mode needs external loop power
- Record as-found before adjusting anything