Skip to content
SenseCalc

HART Loop Load Check

230-1100 ohm window for HART communication.

Inputs

Loop resistance

Loop supply voltage.

Cable + barrier + sampling resistor + indicator.

Result

Total loop resistance (ohm)
250.0
HART OK (1=yes)
1
Calculation details
Below HART window (1=yes)
0
Above HART window (1=yes)
0
Headroom above 230 (ohm)
20.0
Headroom below 1100 (ohm)
850.0

Verify

Check before relying.

HART talks across 230-1100 ohm.

  • Total series resistance measured, not summed
  • Below 230: parallel 250 ohm at the communicator
  • Above 1100: find the extra burden
This calculator is a first-pass screening tool. Verify nameplate data, wiring, module configuration, and calibrator readings before acting.