HART Loop Load Check
230-1100 ohm window for HART communication.
Result
Total loop resistance (ohm)
250.0
HART OK (1=yes)
1
Calculation details
Below HART window (1=yes)
0
Above HART window (1=yes)
0
Headroom above 230 (ohm)
20.0
Headroom below 1100 (ohm)
850.0
Formula
Calculation logicVerify
Check before relying.
HART talks across 230-1100 ohm.
- Total series resistance measured, not summed
- Below 230: parallel 250 ohm at the communicator
- Above 1100: find the extra burden
Related calculators
Loop power
AI Channel Loading
Burden drop plus supply current with verdict.
- Margin per channel (V)
- Supply current (mA)
Loop power
Barrier Drop Budget
Allowed safety-barrier drop with PASS verdict.
- Allowed barrier drop (V)
- Wire + load drop (V)
Loop power
Current to Voltage Resistor
250 ohm 1-5 V selection with power check.
- Resistor (ohm)
- Dissipation (W)
Loop power
HART Loop Capacitance Check
FSK impedance with 150nF verdict.
- Total C (nF)
- Z at 1200Hz (ohm)
Workspace
Keep the assumptions with the result.
Save this calculation to return to the inputs, result, and report from your private workspace.