Skip to content
SenseCalc

RTD Lead Wire Error

2/3/4-wire error estimate.

Inputs

Lead run

Cable run from transmitter to sensor, one way.

Copper section per lead in mm2.

Lead temperature along the run.

100 for PT100, 1000 for PT1000.

Budget

Your accuracy budget for lead error, often 0.25-0.5 C.

Result

2-wire error (C)
8.80
Minimum lead wires (2 or 3)
3
Calculation details
Lead resistance (ohm)
1.720
3-wire residual (C)
0.26

Verify

Check before relying.

Lead ohms are degrees.

  • Wire count matches transmitter (2/3/4)
  • Section and length from the cable schedule
  • 3-wire compensates only matched leads
This calculator is a first-pass screening tool. Verify nameplate data, wiring, module configuration, and calibrator readings before acting.

Related calculators

Workspace

Keep the assumptions with the result.

Save this calculation to return to the inputs, result, and report from your private workspace.

Sign in or create an account to save this calculation.